Exi Optical smoke detectors

An optical smoke detector detects the occurrence of an early-stage fire by measuring the density of the smoke. In the event of an alarming smoke density, an increased current flows through the detector and thus reports the fire to the fire alarm panel.

The optical detector is intended for long-term use because of its robustness and the ability to clean the light chamber in the detector.

It comes in two version:
With one gland - a end base
With tvo glands - a passing base

Rated power supply voltage

12  V DC do 25,2 V DC

Maximum Alarm Current Allowed

45 mA

Electricity at rest

≤30 μA (max. 70 μA)

Permissible operating ambient temperature for

T6 Tamb = -20 do +65⁰ C

Scope of overhead - industry

and a group of gases and vapors or dust

IIC (gases and vapors)
IIIC (dust)

Connection to Fire Alarm Central exclusively via device

SSU-24ExEi

Capacity and inductance by line

It does not affect Lo and Co

Ex protection mark

II 2G Ex ib IIC T6/T4 Gb
II 2D Ex ib IIIC T135C Db

IP protection at the base of the P-802Exi i P-802/1Exi

IP24

Color

White

Weight

300 g.

 

Data sheet

 

Certificate